ATEX junction box and control station, Antidéflagrant Service project (2026)

Every piece of ATEX equipment carries a rating plate that sums up its conditions of use. Here is how to read it, using an example.

Example: CE 0080 · Ex II 2 GD · Ex db IIC T6 Gb · Ex tb IIIC T85 °C Db · LCIE 03 ATEX 6146

ElementMeaning
CE 0080CE marking and number of the notified body that monitors production (here INERIS). The certificate may be issued by a different body (here LCIE)
Ex hexagonSpecific ATEX marking
IIEquipment group: I for mines, II for surface industries
2Category: 1, 2 or 3, depending on the permitted zone
G / DAtmosphere: G for gases, D for dusts
Ex dbType of protection and level: flameproof enclosure, level b
IICGas group: IIA, IIB, IIB+H2 or IIC
T6Temperature class: maximum surface temperature 85 °C
Gb / DbEquipment protection level (EPL)
IIIC T85 °CDust group and maximum surface temperature
LCIE 03 ATEX 6146EU-type examination certificate number

The X or U suffix

  • X at the end of the certificate number (e.g. LCIE 11 ATEX 3062X): specific conditions of use apply. They are given in the instructions.
  • U (e.g. LCIE 03 ATEX 0037U): this is a component, intended to be built into complete equipment.

Further reading: gas groups and temperature classes · ATEX zones